Carrier Chiller Service

Carrier Chiller Service in Moscow

Carrier Chiller Service

Category : chiller service

 

Our customer in Moscow had been emailing our technical support desk regarding the service of his Carrier chillers

Flow Issues

There had been ongoing issues with blocked strainers on the water system. Each time they were cleaned, they blocked back up again. A large dirt trap near to the chiller also needed to be repeatedly cleaned out. A problem with dirt being carried round the water system

Flush Out Service for the Carrier Chillers

The end user had employed a local company for a flush out service for the Carrier Chillers. The company first drained the water system and refilled it with various chemicals. There is a chemical to lift the dirt off the inside of the pipe. Another chemical to carry it back. Another chemical to bond with the heavier elements

Carrier Chiller Service Readings

The readings taken during the Carrier chiller service were wrong by a long shot. There was a serious restriction in flow to the chiller. Safety devices were activated on the chiller to prevent system failure. If not for these safety devices- the chiller would be ruined. More than one device was preventing the chiller from freeze up

0161 370 7193

service@maximuschillers.com

Contact Form

Service of the Water System

The water system was drained down to service the plant. The inlet to the evaporator was removed for inspection. A Considerable amount of sludge was found to be blocking the inlet to the evaporator. The pipe was bolted back on, the water system was refilled then emptied in the reverse direction to the water flow. The water system was filled again and system readings taken

Service to the Carrier Chiller

The service to the Carrier Chiller was found to be satisfactory as the water system readings were okay. No safety devices were being activated and a good run was achieved from the Carrier chiller. All other readings were taken as part of giving the chiller a full heath check. As always a detailed Tick Sheet was completed. Our engineer demonstrated to the on site engineers how to back flush should the issue arise again

Read about legionella and how it can affect a chilled water system on Wikipedia 