Chilled Water System Service of EEV

Chilled Water System EEV Service

Chilled Water System Service of EEV

The Expansion Valve Required Chilled Water System Service

Chilled water system service was being carried out because the mechanical parts of the expansion valve had failed. This particular valve is prone to this fault. It is an OEM part so our technician found the voltage for the motor and found a similar part with the same amount of steps

Electronic EEV Driver

The EEV driver was found to be functioning satisfactorily. Sometimes, depending on how the mechanical part has failed, this can be overloaded and burned out

Electronic Component Refurbishment

Where electronic parts, such as the EEV driver, are found to be burned out- Maximus Chillers has a refurbishment laboratory at head office. We have the capability to strip down the component and fault find where it has blown. Usually it is quite simple: the jammed mechanical part of the electronic expansion valve has burned out the power control on the driver for example. More complex fault finding and component replacement on the circuit board can be carried out also. Another option is to replace the driver with a like for like swap or retrofit to a different driver. In any case- we have the ability for: any part- any problem- any refrigerant anywhere

0161 370 7193

service@maximuschillers.com

Contact Form

Pump Down of the Chilled Water System

The chilled water system was easily valved off and pumped down. This saves on the time and recovery vessel to pump the refrigerant out

Remove and Replace

Once pumped down, our engineer removed and replaced the valve, sealing it on it's knife edge seal. The wire was passed up the conduit and into the panel. The wiring colour scheme was different on the new valve so some time was taken to ensure it was wired up correctly

Open it up and Switch it on

After leak testing, the refrigerant system valves were opened back up and the chilling plant switched back on. The correct superheat and subcooling valued were achieved concluding a successful chilled water system service visit

To read the Institute of Refrigeration guide to expansion valves Click Here